System Selection Guide
Concore System
All Steel System
Woodcore System
60 cm System
Aluminum System
Underfloor Service Devices
Accessories
Finishes
Specifications
Architectural Details
More Information
System Performance Criteria
The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems.  The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.  Panel Only Criteria such as Concentrated Load is often used to specify access floor systems; however, the test is not representative of an actual installation because it is performed with the panel resting on blocks, not understructure. 
System Performance Criteria (Tested on Actual Understructure)
Panel Criteria
(For reference only)
Panel
Understructure SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
CONCENTRATED LOADS @
<
0.010" Perm Set
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
Uniform Loads
(lbs/ft²)
10 Passes
(lbs)
10,000 Passes
(lbs)
WC5000
Cornerlock

6.9

1000 PASS 250 1000 600 150 1000
WC5000
Snap-Tite/
Bolt-Tite

7.4

1000 PASS 250 1000 600 150 1000

*Design loads and safety factors are defined in the Technical Resources/Technical Bulletins area of the website under "Design Loads".  All other tests are conducted under CISCA's Recommended Test Procedure for Access Floors.