The
Performance Charts below are divided
into two sections to help you evaluate
the overall performance of the systems. The
System Performance Criteria are the most
important to consider because they represent
the performance in a typical installation. Panel
Only Criteria such as Concentrated Load
is often used to specify access floor
systems; however, the test is not representative
of an actual installation because it
is performed with the panel resting on
blocks, not understructure.
System
Performance Criteria (Tested on Actual
Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.010" Perm Set
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
WC5000
Cornerlock
6.9
1000
PASS
250
1000
600
150
1000
WC5000
Snap-Tite/
Bolt-Tite
7.4
1000
PASS
250
1000
600
150
1000
*Design
loads and safety factors are defined in the Technical
Resources/Technical Bulletins area of the website
under "Design Loads". All other
tests are conducted under CISCA's Recommended