The
Performance Charts below
are divided into two
sections to help you
evaluate the overall
performance of the systems.
The System Performance Criteria
are the most important to
consider because they represent
the performance in a typical
installation.
Panel Only Criteria
such as Concentrated Load
is often used to specify
access floor systems; however,
the test is not representative
of an actual installation
because it is performed with
the panel resting on blocks,
not understructure.
FF1250
System Performance Criteria
(Tested on Actual Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Solid
Panels
Bolted
Stringer/ Stringerless/
Cornerlock
6.5
1250
2.0
400
150
1000
1000
1250
Perforated
Panels
Bolted
Stringer/ Stringerless/
Cornerlock
6.25
1250
2.0
400
150
1000
1000
1250
Grates
Bolted
Stringer/ Stringerless/
Cornerlock
7.25
1250
2.0
400
150
1000
1000
1250
FF3000
System Performance Criteria
(Tested on Actual
Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
Solid
Panels
Bolted
Stringer/ Stringerless/
Cornerlock
7.60
2250
2.0
750
2000
2000
200
3000
Perforated
Panels
Bolted
Stringer/ Stringerless/
Cornerlock
7.40
2000
2.0
750
1500
2000
100
3000
*A
full definition of Design Loads and
Safety Factors can be found in the
Technical Bulletin section of our
website. All
other tests are conducted under CISCA's
recommended test procedures for access
flooors.