The
Performance Charts below
are divided into two
sections to help you
evaluate the overall
performance of the systems.
The System Performance Criteria
are the most important to
consider because they represent
the performance in a typical
installation.
Panel Only Criteria
such as Concentrated Load
is often used to specify
access floor systems; however,
the test is not representative
of an actual installation
because it is performed with
the panel resting on blocks,
not understructure.
System
Performance Criteria (Tested
on Actual Understructure)
Panel
Criteria
(For reference only)
Panel
Understructure
SYSTEM
WEIGHT
(lbs/ft²)
STATIC
LOADS
ROLLING
LOADS
IMPACT
LOADS
(lbs)
CONCENTRATED
LOADS @
< 0.100"
(lbs)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
Uniform
Loads (lbs/ft²)
10
Passes
(lbs)
10,000
Passes
(lbs)
All
Steel 1000
Bolted
Stringer
6.0
1000
PASS
350
400
400
150
1000
All
Steel 1250
Bolted
Stringer
7.0
1250
PASS
400
500
500
150
1250
All
Steel 1500
Bolted
Stringer
8.5
1500
PASS
450
600
600
150
1500
*Design
loads and safety factors are
defined in the Technical Resources/Technical
Bulletins area of the website
under
"Design Loads". All
other tests are conducted under CISCA's
Recommended Test Procedure for Access
Floors.